Skip to product information
1 of 1

ES Nord 100E

ES Nord 100E

Technical specifications | ES Nord 100E

Rated Heating (A20/W55ºC)
Heating Capacity: 90.00 kW 
Heating Power Input: 19.70 kW
COP: 4.57

Rated Heating One (A7/W45ºC)
Heating Capacity: 95.00 (16.0-100.2) kW 
Heating Power Input: 28.9 (4.5-31.3) kW
COP: 3.29 (3.20-3.56)

Rated Heating Two (A-12/W41ºC)
Heating Capacity: 60.0 (19.1-64.00) kW 
Heating Power Input: 24.7 (6.9-26.7) kW
COP: 2.43 (2.40-2.80)

Rated Heating Three (A-20/W41ºC)
Heating Capacity: 50.9 (16.2-54.5) kW 
Heating Power Input: 25.2 (7.0-27.9) kW
COP: 2.02 (1.95-2.35)

Heating IPLV (H): 3.20
Cooling IPLV (C): 3.90
Power Supply: 380V/3N-/50Hz-60Hz
Max. Power Input: 32.00 kW
Max. Running Current: 51.00 A
Operating Temperature Range -38-55ºC

Water Flow Volume
Hot Water: 15.50 m3/h
Heating (-12/-14ºC): 10.32 m3/h

Water Pressure Drop
Hot Water: 90.00 kPa
Heating (-12/-14ºC): 70.00 kPa

Water Connection: DN65
Noise: 66(56-69) dB(A)
Net Weight: 733 kg
Gross Weight: 833 kg
Net Dimensions (L/W/H): 2170x1150x2130

 _____________________

Rated heating: outdoor dry/wet bulb temperature is 20/15°C, initial water temperature is 15°C, target water temperature is 55°C, circulating heating temperature difference is 5°C

Normal temperature heating: outdoor dry/wet bulb temperature is 7/6°C, unit inlet and outlet water temperature is 40/45°C Low temperature heating: The outdoor dry/wet bulb temperature is -12/-14°C, and the unit outlet water temperature is 41°C Ultra-low temperature conditions: the outdoor dry bulb temperature is -20°C, and the unit outlet water temperature is 41°C

Nominal cooling: outdoor dry/wet bulb temperature is 35/24°C, unit outlet water temperature is 7°C, unit inlet water temperature is 12°C



*Note: The shown version and color of the heat pump may vary.

View full details